The West Jordan City Building & Safety Division uses the following design criteria when reviewing projects submitted for a building permit within City limits.


  1. BUILDING CODES: The Building Division enforces the following building codes with State of Utah amendments.
    • 2024 International Building Code (including Appendices C & J)
    • 2021 International Residential Code (including Appendix AQ)
    • 2024 International Plumbing Code
    • 2024 International Mechanical Code
    • 2024 International Fuel Gas Code
    • 2023 National Electric Code
    • 2024 International Energy Conservation Code
    • 2024 International Existing Building Code
    • 2024 International Swimming Pool and Spa Code (residential provisions only)
    • 2024 International Fire Code
    • ICC A117.1-2009 – Accessibility Standard
    • City of West Jordan – Title 10 Building Regulations
  2. SNOW LOADS:
    1. Residential: The ground snow loads shall be determined using the following website: https://utahsnowload.usu.edu
    2. Commercial: The ground snow loads shall be determined using the ASCE Hazard Tool: https://ascehazardtool.org/
    3. Roof Snow Loads:
      • Shall be determined per Chapter 7 of ASCE 7-22.
      • At locations where the roof snow load exceeds 45 psf, a percentage of the snow load must be considered in the effective seismic weight of the structure per Section 15A-3-107 of the Utah Amended Code.
  3. WIND:
    1. Speed: All wind speeds listed below are 3-second gusts at 33 feet above the ground.
      • Residential: 105 mph
      • Commercial (see IBC Figures 1609.3(1–4)):
        • Risk Category I = 95–100 mph (see IBC Figure 1609.3(1))
        • Risk Category II = 100–105 mph (see IBC Figure 1609.3(2))
        • Risk Category III = 105–110 mph (see IBC Figure 1609.3(3))
        • Risk Category IV = 110–115 mph (see IBC Figure 1609.3(4))
    2. Exposure: Site specific (per Section 1609.4 of the IBC). Assumed to be “C” unless justified.
  4. SEISMIC:
    1. Seismic Design Category:
      • Residential: D2
      • Commercial: D
    2. Site-specific: Because ground motions vary throughout the city, the mapped and design ground motions (SS, SDS, S1, SD1) should be obtained using the site-specific address or latitude/longitude in the ASCE Hazard Tool: https://ascehazardtool.org/
  5. SOILS:
    1. Frost Depth: 30 inches.
    2. Site Class: Site specific. See geotechnical report for site class.
    3. Residential: 1,500 psf per IRC Table R401.4.1, unless stated otherwise in a geotechnical report.
    4. Commercial: Site-specific geotechnical report required for all new buildings.
    5. Site-specific Geotechnical Report: All geotechnical reports submitted for permit issuance must be dated no later than two years from the permit application date. Outdated reports must be accompanied by a letter from a qualified geotechnical engineer stating that the report requirements are still valid or explaining what items may have changed.
  6. FLOOD HAZARDS:
    1. Flood Hazard Areas:
      • Residential: Buildings and structures located in flood hazard areas (Flood Zones A or V) must comply with IRC R322.
      • Commercial: Buildings and structures located in flood hazard areas must comply with IBC 1612, Chapter 5 of ASCE 7-22, and ASCE 24-14.
    2. Floodways: Buildings and structures located in identified floodways must be designed and constructed in accordance with ASCE 24-14.
    3. Interactive Flood Zone Map:
      https://gis.wjordan.com/flood-zones/
  7. RAINFALL: Average annual rainfall is 16 inches.
  8. CLIMATE ZONE: 5B
  9. WEATHERING: Severe
  10. TERMITE: None to Slight
  11. WINTER DESIGN TEMP: 8°F
  12. ICE SHIELD UNDERLAYMENT: Yes
  13. AIR FREEZING INDEX: ≤ 1000
  14. MEAN ANNUAL TEMP: 45°F

 

Last Revised: 07/2026